Below is an extract from our in house specification book comparing the brands of gas fired, commercial wall hung boilers currently on the market. This provides a comparison for all the commercial boilers when specifying boilers for a particular project. This is a quick and easy guide to finding the correct boilers that would most suit the application. By clicking the link on each boiler you can find the full data sheet for each boiler to go more in depth on the specifications however this chart provides the basics and most of what you need to know.

 

Remeha

Model Integral pump Heat output at 80/60 (kW) Size

D x H x W

eight dry (Kg) Standard Flue Size Heat Exchanger Efficiency (%)
GCV NCV
Quinta Ace 45 No 40 500x750x500 53 80/125 Cast Aluminium 89.3 99.1
Quinta Ace 55 No 55.3 500x750x500 56 100/150 Cast Aluminium 88.1 97.8
Quinta Ace 65 No 61.5 500x750x500 60 100/150 Cast Aluminium 89.4 99.2
Quinta Ace 90 No 84.2 500x750x500 67 100/150 Cast Aluminium 88.2 97.9
Quinta Ace 115 No 107 500x750x500 68 100/150 Cast Aluminium 87.5 97.1
Quinta Ace 160 No 152.9 600x1045x602 147 100/150 Cast Aluminium 87.8 97.5

 

Ideal

Model

Integral pump Heat output at 80/60 (kW) Size

D x H x W

Weight dry (Kg) Standard Flue Size Heat Exchanger Efficiency (%)
GCV

NCV

Evomax 2 40

No

40 360x850x500 47.5 80/125 Cast Aluminium 89.3 99.4
Evomax 2 60

No

60 360x850x500 57.5 80/125 Cast Aluminium 89.4

99.6

Evomax 2 80

No 80 360x850x500 57.5 80/125 Cast Aluminium N/A

99

Evomax 2 100

No

100 360x850x500 73 100/150 Cast Aluminium N/A

98.2

Evomax 2 120

No

120 360x850x500 73 100/150 Cast Aluminium N/A

98

Evomax 2 150

No

150 610x850x500 81 100/150 Cast Aluminium N/A

98.2

 

 

Hamworthy

Model

Integral pump Heat output at 80/60 (kW) Size

D x H x W

Weight dry (Kg) Standard Flue Size Heat Exchanger Efficiency (%)
GCV

NCV

Stratton MK S2-40

No

40 477x890x541 50 80/125 Stainless Steel 89

95.75

Stratton MK S2-60 No 56.4 477x890x541 60 80/125 Stainless Steel 89.2

96.13

Stratton MK S2-70

No

69.9 574x890x541 90 100/150 Stainless Steel 88.8

95.5

Stratton MK S2-80

No

79.8 574x890x541 90 100/150 Stainless Steel 88.8

95.5

Stratton MK S2-100

No

95.7 574x890x541 95 100/150 Stainless Steel 89.1

96.02

Stratton MK S2-120

No

119.5 574x890x541 100 100/150 Stainless Steel 89.1

95.95

 

 

Viessmann

Model

Integral pump Heat output at 80/60 (kW) Size

D x H x W

Weight dry (Kg) Standard Flue Size Heat Exchanger Efficiency (%)
GCV

NCV

Vitodens 200-w 49

No

45 380x850x480 65 80/125 Stainless Steel N/A

N/A

Vitodens 200-w 60

No

55.2 380x850x480 65 80/125 Stainless Steel N/A

N/A

Vitodens 200-w 80

No

74.1 530x850x480 83 100/150 Stainless Steel N/A

N/A

Vitodens 200-w 99

No

90.9 530x850x480 83 100/150 Stainless Steel N/A

N/A

Vitodens 200-w 120

No

110.9 690x900x600 130 100/150 Stainless Steel N/A

N/A

Vitodens 200-w 150

No 136.0 690x900x600 130 100/150 Stainless Steel N/A

N/A

 

 

Vaillant

Model

Integral pump Heat output at 80/60 (kW) Size

D x H x W

Weight dry (Kg) Standard Flue Size Heat Exchanger Efficiency (%)
GCV

NCV

ecoTEC 48

Yes

44.1 405x720x440 38 80/125 Stainless Steel N/A

98.2

ecoTEC 64

Yes

58.7 473x720x440 48 80/125 Stainless Steel N/A

98.2

ecoTEC 80 No 74.7 602x960x480 68 100/150 Stainless Steel N/A

97.0

ecoTEC 100

No

93.3 602x960x480 86 100/150 Stainless Steel N/A

98.0

ecoTEC 120

No

112.0 602x960x480 90 100/150 Stainless Steel N/A

98.0

 

Potterton Commercial

Model

Integral pump Heat output at 80/60 (kW) Size

D x H x W

Weight dry (Kg) Standard Flue Size Heat Exchanger Efficiency (%)
GCV

NCV

Sirius Three 50

No

45.1 377x763x450 40 80/125 Stainless Steel 87.8

96.6

Sirius Three 60

No

55.0 377x763x450 40 80/125 Stainless Steel 87.6

96.4

Sirius Three 70

No

65.1 505x763x450 50 110/160 Stainless Steel 87.6

96.1

Sirius Three 90

No

85.1 584x952x600 83 110/160 Stainless Steel 87.7

96.5

Sirius Three 110

No

102 584x952x600 93 110/160 Stainless Steel 87.6

96.4

Sirius Three 130

No

121 584x952x600 93 110/160 Stainless Steel 88.4

97.3

Sirius Three 150 No 140 584x952x600 96 110/160 Stainless Steel 88.4

97.3

 

Potterton Commercial

Model

Integral pump Heat output at 80/60 (kW) Size

D x H x W

Weight dry (Kg) Standard Flue Size Heat Exchanger Efficiency (%)
GCV

NCV

Paramount five 40

No

36.8 407x852x480 53 80/125 Cast Aluminium N/A

95.3

Paramount five 50

No

48.7 447x852x480 61 110/160 Cast Aluminium N/A

95.6

Paramount five 60

No

56.4 447x852x480 61 110/160 Cast Aluminium N/A

95.7

Paramount five 80

No

74.9 542x852x480 72 110/160 Cast Aluminium N/A

96.2

Paramount five 95

No 92.5 470x852x480 84 110/160 Cast Aluminium N/A

95.8

Paramount five 115

No

111.7 570x852x480 84 110/160 Cast Aluminium N/A

95.7

 

Elco

Model

Integral pump Heat output at 80/60 (kW) Size

D x H x W

Weight dry (Kg) Standard Flue Size Heat Exchanger Efficiency (%)
GCV

NCV

Thision L Evo 60

No

56.5 590x810x630 83 80/125 Stainless Steel 87.9

97.6

Thision L Evo 70

No

65.5 590x810x630 83 80/125 Stainless Steel 88.3

98.0

Thision L Evo 80

No

75.3 590x810x630 83 80/125 Stainless Steel 88.3

98.0

Thision L Evo 100

No

92.9 590x950x630 96 100/150 Stainless Steel 87.9

97.6

Thision L Evo 120

No

111.9 590x950x630 96 100/150 Stainless Steel 88.2

97.9

Thision L Evo 140

No

130.4 590x950x630 96 100/150 Stainless Steel 88.1

97.8

 