Wall Mounted Commercial Boiler Comparison
Below is an extract from our in house specification book comparing the brands of gas fired, commercial wall hung boilers currently on the market. This provides a comparison for all the commercial boilers when specifying boilers for a particular project. This is a quick and easy guide to finding the correct boilers that would most suit the application. By clicking the link on each boiler you can find the full data sheet for each boiler to go more in depth on the specifications however this chart provides the basics and most of what you need to know.
Remeha
Model | Integral pump | Heat output at 80/60 (kW) | Size
D x H x W |
eight dry (Kg) | Standard Flue Size | Heat Exchanger | Efficiency (%) | |
GCV | NCV | |||||||
Quinta Ace 45 | No | 40 | 500x750x500 | 53 | 80/125 | Cast Aluminium | 89.3 | 99.1 |
Quinta Ace 55 | No | 55.3 | 500x750x500 | 56 | 100/150 | Cast Aluminium | 88.1 | 97.8 |
Quinta Ace 65 | No | 61.5 | 500x750x500 | 60 | 100/150 | Cast Aluminium | 89.4 | 99.2 |
Quinta Ace 90 | No | 84.2 | 500x750x500 | 67 | 100/150 | Cast Aluminium | 88.2 | 97.9 |
Quinta Ace 115 | No | 107 | 500x750x500 | 68 | 100/150 | Cast Aluminium | 87.5 | 97.1 |
Quinta Ace 160 | No | 152.9 | 600x1045x602 | 147 | 100/150 | Cast Aluminium | 87.8 | 97.5 |
Ideal
Model |
Integral pump | Heat output at 80/60 (kW) | Size
D x H x W |
Weight dry (Kg) | Standard Flue Size | Heat Exchanger | Efficiency (%) | |
GCV |
NCV |
|||||||
Evomax 2 40 |
No |
40 | 360x850x500 | 47.5 | 80/125 | Cast Aluminium | 89.3 | 99.4 |
Evomax 2 60 |
No |
60 | 360x850x500 | 57.5 | 80/125 | Cast Aluminium | 89.4 |
99.6 |
No | 80 | 360x850x500 | 57.5 | 80/125 | Cast Aluminium | N/A |
99 |
|
Evomax 2 100 |
No |
100 | 360x850x500 | 73 | 100/150 | Cast Aluminium | N/A |
98.2 |
Evomax 2 120 |
No |
120 | 360x850x500 | 73 | 100/150 | Cast Aluminium | N/A |
98 |
Evomax 2 150 |
No |
150 | 610x850x500 | 81 | 100/150 | Cast Aluminium | N/A |
98.2 |
Hamworthy
Model |
Integral pump | Heat output at 80/60 (kW) | Size
D x H x W |
Weight dry (Kg) | Standard Flue Size | Heat Exchanger | Efficiency (%) | |
GCV |
NCV |
|||||||
Stratton MK S2-40 |
No |
40 | 477x890x541 | 50 | 80/125 | Stainless Steel | 89 |
95.75 |
Stratton MK S2-60 | No | 56.4 | 477x890x541 | 60 | 80/125 | Stainless Steel | 89.2 |
96.13 |
Stratton MK S2-70 |
No |
69.9 | 574x890x541 | 90 | 100/150 | Stainless Steel | 88.8 |
95.5 |
Stratton MK S2-80 |
No |
79.8 | 574x890x541 | 90 | 100/150 | Stainless Steel | 88.8 |
95.5 |
Stratton MK S2-100 |
No |
95.7 | 574x890x541 | 95 | 100/150 | Stainless Steel | 89.1 |
96.02 |
Stratton MK S2-120 |
No |
119.5 | 574x890x541 | 100 | 100/150 | Stainless Steel | 89.1 |
95.95 |
Viessmann
Model |
Integral pump | Heat output at 80/60 (kW) | Size
D x H x W |
Weight dry (Kg) | Standard Flue Size | Heat Exchanger | Efficiency (%) | |
GCV |
NCV |
|||||||
Vitodens 200-w 49 |
No |
45 | 380x850x480 | 65 | 80/125 | Stainless Steel | N/A |
N/A |
Vitodens 200-w 60 |
No |
55.2 | 380x850x480 | 65 | 80/125 | Stainless Steel | N/A |
N/A |
Vitodens 200-w 80 |
No |
74.1 | 530x850x480 | 83 | 100/150 | Stainless Steel | N/A |
N/A |
Vitodens 200-w 99 |
No |
90.9 | 530x850x480 | 83 | 100/150 | Stainless Steel | N/A |
N/A |
Vitodens 200-w 120 |
No |
110.9 | 690x900x600 | 130 | 100/150 | Stainless Steel | N/A |
N/A |
No | 136.0 | 690x900x600 | 130 | 100/150 | Stainless Steel | N/A |
N/A |
Vaillant
Model |
Integral pump | Heat output at 80/60 (kW) | Size
D x H x W |
Weight dry (Kg) | Standard Flue Size | Heat Exchanger | Efficiency (%) | |
GCV |
NCV |
|||||||
ecoTEC 48 |
Yes |
44.1 | 405x720x440 | 38 | 80/125 | Stainless Steel | N/A |
98.2 |
ecoTEC 64 |
Yes |
58.7 | 473x720x440 | 48 | 80/125 | Stainless Steel | N/A |
98.2 |
ecoTEC 80 | No | 74.7 | 602x960x480 | 68 | 100/150 | Stainless Steel | N/A |
97.0 |
ecoTEC 100 |
No |
93.3 | 602x960x480 | 86 | 100/150 | Stainless Steel | N/A |
98.0 |
ecoTEC 120 |
No |
112.0 | 602x960x480 | 90 | 100/150 | Stainless Steel | N/A |
98.0 |
Potterton Commercial
Model |
Integral pump | Heat output at 80/60 (kW) | Size
D x H x W |
Weight dry (Kg) | Standard Flue Size | Heat Exchanger | Efficiency (%) | |
GCV |
NCV |
|||||||
Sirius Three 50 |
No |
45.1 | 377x763x450 | 40 | 80/125 | Stainless Steel | 87.8 |
96.6 |
Sirius Three 60 |
No |
55.0 | 377x763x450 | 40 | 80/125 | Stainless Steel | 87.6 |
96.4 |
Sirius Three 70 |
No |
65.1 | 505x763x450 | 50 | 110/160 | Stainless Steel | 87.6 |
96.1 |
Sirius Three 90 |
No |
85.1 | 584x952x600 | 83 | 110/160 | Stainless Steel | 87.7 |
96.5 |
Sirius Three 110 |
No |
102 | 584x952x600 | 93 | 110/160 | Stainless Steel | 87.6 |
96.4 |
Sirius Three 130 |
No |
121 | 584x952x600 | 93 | 110/160 | Stainless Steel | 88.4 |
97.3 |
Sirius Three 150 | No | 140 | 584x952x600 | 96 | 110/160 | Stainless Steel | 88.4 |
97.3 |
Potterton Commercial
Model |
Integral pump | Heat output at 80/60 (kW) | Size
D x H x W |
Weight dry (Kg) | Standard Flue Size | Heat Exchanger | Efficiency (%) | |
GCV |
NCV |
|||||||
Paramount five 40 |
No |
36.8 | 407x852x480 | 53 | 80/125 | Cast Aluminium | N/A |
95.3 |
Paramount five 50 |
No |
48.7 | 447x852x480 | 61 | 110/160 | Cast Aluminium | N/A |
95.6 |
Paramount five 60 |
No |
56.4 | 447x852x480 | 61 | 110/160 | Cast Aluminium | N/A |
95.7 |
Paramount five 80 |
No |
74.9 | 542x852x480 | 72 | 110/160 | Cast Aluminium | N/A |
96.2 |
Paramount five 95 |
No | 92.5 | 470x852x480 | 84 | 110/160 | Cast Aluminium | N/A |
95.8 |
Paramount five 115 |
No |
111.7 | 570x852x480 | 84 | 110/160 | Cast Aluminium | N/A |
95.7 |
Elco
Model |
Integral pump | Heat output at 80/60 (kW) | Size
D x H x W |
Weight dry (Kg) | Standard Flue Size | Heat Exchanger | Efficiency (%) | |
GCV |
NCV |
|||||||
Thision L Evo 60 |
No |
56.5 | 590x810x630 | 83 | 80/125 | Stainless Steel | 87.9 |
97.6 |
Thision L Evo 70 |
No |
65.5 | 590x810x630 | 83 | 80/125 | Stainless Steel | 88.3 |
98.0 |
Thision L Evo 80 |
No |
75.3 | 590x810x630 | 83 | 80/125 | Stainless Steel | 88.3 |
98.0 |
Thision L Evo 100 |
No |
92.9 | 590x950x630 | 96 | 100/150 | Stainless Steel | 87.9 |
97.6 |
Thision L Evo 120 |
No |
111.9 | 590x950x630 | 96 | 100/150 | Stainless Steel | 88.2 |
97.9 |
Thision L Evo 140 |
No |
130.4 | 590x950x630 | 96 | 100/150 | Stainless Steel | 88.1 |
97.8 |